• Power Cable UL Type TC or TC-ER

    Applications

    As flame-retardant three or four conductor power cables rated 600V, 90掳C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.

    Construction

    Class B stranded uncoated copper conductor, FR-XLPE flame-retardant cross-linked polyethylene insulation, surface print phase identification. Three or four insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and suitable fillers,聽 cable tape, helical copper tape shield, PVC jacket overall, surface printed

    Standards

    • Listed by UL as Type TC per Standard 1277 for Tray Cables.
    • Individual conductors UL listed as Type XHHW-2.
    • Individual conductors pass UL VW-1 flame test.
    • Overall jacket UL listed as Sunlight Resistant and Oil Resistant II.
    • Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
    • Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
    • Cables UL listed for Direct Burial.
    • Cables UL listed for Open Wiring.
    • Cables meet requirements of ICEA S-95-658/NEMA WC70.
    • Color Code ICEA Method 4.
    • Ampacity in accordance with the National Electrical Code for cables in uncovered cable tray without maintained spacing and for cables in raceway or directly buried; at the conductor temperature indicated, in wet or dry locations, 30掳C ambient temperature.
    • Grounding conductor per UL Standard 1277 for Type TC Tray Cable.