• ASTM B230 – Aluminum 1350–H19 Wire for Electrical Purposes
• ASTM B231 – Concentric-Lay-Stranded Aluminum 1350 Conductors
• ASTM B232 – Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)
• ASTM B498 – Zinc-Coated (Galvanized) Steel Core Wire for Use in Overhead Electrical Conductors
• CSA C60888 – Zinc-coated steel wires for stranded conductors
• CSA C60889 – Hard-drawn aluminum wire for overhead line conductors
• CSA C61089 – Round wire concentric lay overhead electrical stranded conductors
Options
CLICK THE LINKS BELOW FOR MORE INFO:
NOTES
1) Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.
2) Resistance is calculated using metal conductivity of 61.2% IACS for EC (1350) at 20ºC and 8% IACS for steel at 20ºC.
3) Ampacities are based on 75ºC conductor temperature, 25ºC ambient, 2 ft/s wind, full sun, an emissivity of 0.5 and a coefficient of solar absorption of 0.5, at sea level.
UPDATED 07/14/2023
Code Name |
N/A Condor |
Meets
|
N/A Yes |
Size
|
N/A 795 |
Stranding
|
N/A 54/7 |
Wire
|
N/A 0.1213 |
Wire
|
N/A 0.1213 |
Diameter
|
N/A 0.3639 |
Diameter
|
N/A 1.092 |
Weight
|
N/A 748.4 |
Weight
|
N/A 273.9 |
Weight
|
N/A 1022.2 |
Rated
|
N/A 28200 |
Resistance
|
N/A 0.022 |
Allowable
|
N/A 889 |