* Unless specifically permitted in 240.4(E) through (G), the overcurrent protection shall not exceed 15 amperes for 14 7m视频, 20 amperes for 12 7m视频, and 30 amperes for 10 7m视频 copper; or 15 amperes for 12 7m视频 and 25 amperes for 10 7m视频 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.
See the NEC for conductor ampacities, correction factors, and conditions of use.